Model Sw45 Series Sw45-4000 Intelligent Air Circuit Breaker/Acb

Breaking Capacity: Low Voltage Circuit Breakers
Operation: Manual Type
Speed: High-Speed Circuit Breaker
Arc-extinguishing Medium: Air
Installation: Fixed
Structure: Universal
Customization:
Diamond Member Since 2016

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
SW45-4000
Certification
ISO9001-2000, CE, CB, CCC
Number of Poles
3p 4p
Nominal Insulation Voltage Ui
690V 1000V 1000V
Electrical Life
1000, 1000, 500
Frequency of Operation (Number of Times
20,10,10,
Transport Package
Export Carton
Specification
IEC60947-2
Trademark
Tengen/OEM
Origin
China
Production Capacity
1000 Pieces/Week

Product Description

1. Product Introduction:
With a rated current from 200A to 6300A, and rated operational voltage 415V 690V, 50Hz, the NA8G series air circuit breaker (hereinafter referred to as "breaker") is mainly used in the distribution network to distribute electric energy and protect lines and power equipment from being damaged by overload, under voltage, short circuit, single-phase grounding and other failures.
Having art-oriented appearance, high breaking capacity, zero arcover and vanities of intellectualized protection functions, that breaker can be used for selective protection with accurate action, no unnecessary power cut, and better power supply reliability.
The product allows the wire to enter or enter from the lower port, and the open frame (draw-out) circuit breaker has isolation function.
That breaker can be widely used for power stations, factories, mines and modern tall buildings, especially the distribution system in the intelligent building, and also widely used in green projects such as wind and solar power generation.
This product meets the requirements in IEC/EN 60947-2
2.Operation conditions
2..1 When theambientair temperature is-5C - +40 C, the mean value is no greater than +35C within 24 hours.
Note: Ifthe upper limit is higherthan +40C or lower limit lower than -5C in work, discussions shall be made between the user and the manufacture
2.2 Altitude: not higher than 2000m for the installation site.
2.3 When the ambient air temperature is +40C, the relative humidity of the air shall not be higher than 50%;a higher relative humidity is allowed at a lower temperature; for example, forthe wettest month, the maximum relative humidity averaged shall be 90% while the lowest temperature averaged in that month + 20C , and special measures shall betakenforthecondensation occasionally produced due to temperature change.
2.4 Class of pollution: 3
2.5
 The installation category of the breaker' main circuit is IV; when the rated operational voltage of the main circuit is less than or equal to AC400V, The installation category of the control circuit and auxiliary circuit is III, apart from the similarity between the under voltage release coil and the intellectual controller's power transformer primary coil and the breaker;When the rated operational voltage of the major loop is greater than AC400V and less than or equal to AC690V, it is necessary for the control circuit and auxiliary circuit to be isolated from the major loop, and the highest operational voltage of the control circuit and auxiliary circuit is AC400V, the installation category of the control circuit and auxiliary circuit being III.
3. Main technical parameters
Shell grade rated current Inm A 1600 3200 6300
Rated current In A   200,400,630,800,
1000,1250,1600
1600,2000,2500,
2900,3200
4000,5000 6300
Nominal insulation voltage Ui V 690 1000 1000  
Rated operational voltage Ue V 415 690 415 690 415  
Rated ultimate short circuit breaking capacity leu kA 50 25 100 65 120  
Rated service short circuit breaking capacity les kA 40 20 80 65 100  
Rated short time withstand current lcw,1s kA 40 20 80 65 100  
Number of poles   3P 4P 3P 4P 3P 4P 3P
Frequency of operation (number of times/h) 20 10 10  
  Mechanical life 3000 3000 2000  
Number of operations Electrical Life 1000 1000 500  
Flashover distance mm   0 0 0  
Line incoming pattern   Wire to enter from the upper or lower port Wire to enter from the upper or lower port Wire to enter from the upper or lower port  
  fixed type kg 22/26.5 52.5/66.5 -  
Net weight (3 poles/4 poles) draw-out type kg 42.5/55 98/121 210/233 233
Size(3 poles/4 poles) fixed type 320x(254/324)x258 406x(422/537)x329 -  
Height x width x depth draw-out type 351 x(282/352)x352 439x(435/550)x445 439x(835/928)x501 439x928x501