Standard | IEC/EN 60898-1,IEC60947-2 | |||||||
Rated current In | A | 1, 2, 3, 4, 6,10,16,20,25,32, 40, 50, 63 | ||||||
Poles | 1P, 1P+N,2P,3P,3P+N, 4P | |||||||
Rated voltage Ue | V | 230/400~240/415 | ||||||
Insulation voltage Ui | V | 500 | ||||||
Rated frequency | 50/60Hz | |||||||
Rated breaking capacity | A | 4500 | ||||||
Energy limiting class | 3 | |||||||
Rated impulse withstand voltage(1.2/50) Uimp | V | 6000 | ||||||
Dielectric test voltage at ind. Freq. for 1 min | kV | 2 | ||||||
Pollution degree | 2 | |||||||
Power loss per pole | Rated current (A) | Max power loss per pole (W) | ||||||
1, 2, 3, 4, 5, 6, 10 | 2 | |||||||
13, 16, 20, 25, 32 | 3.5 | |||||||
40, 50, 63 | 5 | |||||||
Thermo-magnetic release characteristic | B, C, D | |||||||
Electrical life | 4, 000 | |||||||
Mechanical life | 20, 000 | |||||||
Contact position indicator | Yes | |||||||
Protection degree | ºC ºC |
IP20 30 -5...+40(Special application please refer to P14 for temperature compensation correction) |
||||||
Reference temperature for setting | ||||||||
of thermal element | ||||||||
Ambient temperature (with | ||||||||
daily average≤35ºC) | ||||||||
Storage temperation | ºC | -25...+70 | ||||||
Terminal connection type | Cable/U-type busbar/Pin-type busbar | |||||||
Terminal size top/bottom for cable |
mm2 | 25 | ||||||
AWG | 18-4 | |||||||
Tightening torque |
N·m | 2.5 | ||||||
In-Ibs. | 22 | |||||||
Mounting | On DIN rail EN 60715 (35mm) by means of fast clip device | |||||||
Connection | From top and bottom | |||||||
Auxiliary contact | Yes | |||||||
Shunt release | Yes | |||||||
Under voltage release | Yes | |||||||
Alarm contant | Yes |