• 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
  • 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
  • 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
  • 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
  • 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
  • 1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka

1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka

Breaking Capacity: Low Voltage Circuit Breakers
Operation: Electric Type
Speed: High-Speed Circuit Breaker
Arc-extinguishing Medium: Air
Installation: Fixed
Structure: RCCB
Samples:
US$ 15/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2016

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Model NO.
SRE7-63
Poles Number
1p+N, 3p+N
Type
Circuit Breaker
Function
Circuit-Breaker Failure Protection, Residual Current Protection
Certification
ISO9001-2000, CE, CB, CCC
-Rated Voltage Un
230 / 400VAC
Tripping  Category
Electromagnetic
Trademark
LONGROAD/OEM
Origin
China
Production Capacity
200000PCS/Month

Product Description

1. General
1.1 Function
Control electric circuits.
Protect people against indirect contacts and additional
protection against direct contacts.
Protect installations against fire hazard due to insulation
faults.
Residual current circuit breakers are used in housing, tertiary
sector and industry.
1.2 Selection
Detectable wave form
AC class
Tripping is ensured for slowly increasing sinusoidal AC
residual currents.
A class
Tripping is ensured for sinusoidal AC residual currents and
for pulsed DC residual currents, whether applied suddenly
or increasing slowly.
Tripping sensitivity
10mA - precision instrument leakage protection and
bathroom use.
30mA - additional protection against direct contact.
300mA - protection against indirect contacts, as well as fire
hazard.
Tripping time
Instantaneous
It ensures instantaneous tripping (without time-delay).
2.Technical data
  Standard   IEC/EN 61008-1






Electrical features
Type (wave form of the earth leakage sensed)   AC, A
Rated current In A 16, 25, 32, 40, 63
Poles   1P+N, 3P+N
Rated voltage Ue V 230/400~240/415,110/200~127/220
Rated sensitivity I△n A 0.01 (Only for 1P+N 16A, 25A),0.03,0.3
Insulation voltage Ui V 500
Rated residual making and breaking capacity I△m A 500 (In=16A/25A/32A/40A)
630 (In=63A)
Short-circuit current Inc=Ic A 6000/10000
SCPD fuse A 10000
break time under I△n s ≤0.1
Rated frequency Hz 50/60
Rated impulse withstand voltage(1.2/50) Uimp V 6000
Dielectric test voltage at ind. Freq. for 1 min kV 2
Pollution degree   2


Mechanical features
Electrical life   2, 000
Mechanical life   2, 000
Fault current indicator   Yes
Protection degree   IP20
Ambient temperature (with daily average≤35ºC) ºC -5...+40
Storage temperation ºC -25...+70




Installation
Terminal connection type
Terminal size top/bottom for cable

Terminal size top/bottom for busbar

mm2
Cable/U-type busbar/Pin-type busbar
25
AWG
mm2
18-3
10
AWG 18-8
Tightening torque N·m 2.5
In-Ibs. 22
Mounting   On DIN rail EN 60715 (35mm) by means of fast clip device
Connection   From top and bottom
1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka
1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka1p+N and 3p+N Magnetic RCCB Short-Circuit Breaking Capacity 10ka

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now