1 Scope of application
LRPG Series circuit breaker with residual current protection is a high-performance adjustable circuit breaker with triple protection functions of leakage, overload and short circuit. lt is applicable to AC 50/60Hz and rated voltage 230/240V. Places with rated current of 60A and below. lt is mainly used for electric leakage, overload and short circuit protection of lighting, energy meter boxes, distribution lines and equipment of residential buildings, office buildings and similar buildings, and can also be used for infrequent operation and switching of lines under normal conditions.
2)The product standard
IEC/EN 60947-2, NFC 61450
3 Product features
Compact structure, multiple rated current ranges can be selected,which can solve the problem of frequent replacement of circuit breakers due to increasing load.
4. Main technical parameter
4.1
Type |
LRPG |
Poles |
3P+N |
Rated Current(A) |
10~30A(10,15,20,25,30)A 30~60A(30,40,50,60)A |
Rated Voltage(V) |
230V/400V |
Leakage operating current(mA) |
300/500mA |
leakage non -operating current(mA) |
150mA/250mA |
Short-circuit Breaking Capacity Icn (A) |
4500A |
Rated frequency:(Hz) |
50/60Hz |
Electrical Life(times) |
1500 |
Mechanical Life(times) |
8500 |
Note: breaking capacity 6000A: rated operation breaking capacity lcs=rated limit breaking Capacity lcu=6000A
4.2
Reference temperature |
Current multiple |
Current name |
Action time |
+40ºC |
non tripping current |
1.05Ir |
≥1h |
|
tripping current |
1.3Ir |
<1h |
Note: breaking capacity 6000A: rated operation breaking capacity lcs=rated limit breaking Capacity lcu=6000A
4.3
Residual current (mA) |
300,500 |
Remaining protection electric life(times) |
3000 |
Setting value of short-circuit protection |
10In |
Type of residual current release |
ELM |
Using type |
A |
Rated impulse withstand voltage(KV) |
6 |
Residual current protection type |
AC |
Note: ELM is the electromagnetic tripping type product used for the residual current release of the product; Type A Residual current
protection is used to protect for sinusoidal AC residual currents and DC residual currents
Type AC Residual current protection is used to protect for sinusoidal AC residual currents.
4.3
Reference temperature |
Current multiple |
Current name |
Action time |
+40ºC |
non tripping current |
1.05Ir |
≥1h |
tripping current |
1.3Ir |
<1h |
5.operating principles
5.1 Service connections are the interface between the Utility and the end- user customer.
5.2 They connect the customer's electrical installation to the power distribution network.
6. Advantages
6.1 Low-cost product,suitable for conventional service connections.
6.2 Multiple rating device.
6.3 Several levels of earth leakage sensitivity.
6.4 Complies with the French NFC 61450 standard.
7. Convenience and safety
7.1Prevention of over-voltage
The neutral pole is designed to close first and open last to maintain a fixed potential.
7.2 Protection against nuisance tripping
Immunized against voltage surges of atmospheric origin
Uninterrupted power supply for greater user convenience
7.3 Safety checking
·The test button may be used to simulate an earth leakage fault, thereby providing a simple way to check the system.
7.4 Easy operation
Operation in all positions
ON/OFF control by push-button
Rating easily changed
lead-saleable terminal shields
captive terminal screws
pivoting terminals
copper cables up to 35 mm²
neutral identified in blue
8.Series model specification and its meaning
LRPG-2P/ LRPG: company model, 2P:1P+N, rated current
9 Normal installation and working conditions
a) Working environment of LRPG products is -5°C~40 'C, humidity≤ 95%;
b) The altitude of the installation site shall not exceed 2000m; Note: lf the altitude of the installation site exceeds 2000m, the use of the circuit breaker shall be negotiated with the manufacturer.
c)Special measures shall be taken for occasional condensation due to temperature change;
d)Installation position: no obvious shaking, impact vibration, explosive corrosive gas, rain and snow;
e) Installation conditions: the external magnetic field of the installation site shall not exceed 5 times of the geomagnetic field in any direction;
f) Installation category: ll or ll;
g) Pollution level: 3;
h)Transportation and storage conditions: the product storage and transportation environment shall be dry and ventilated, free from significant impact and vibration, direct sunlight, rain, dust, chemical gas corrosion,etc
10.Boundary and installation dimensions (unit: mm)

M4 screws are recommended to be used as the mounting screws, andthe mounting dimensions are shown in the dimension drawing above.
Table of sectional area of product wire connection
Rated Current In/A |
In<6A |
6A<In≤13A |
13A<In≤20A |
20A<In≤25A |
25A<In≤32A |
32A<In≤50A |
50A<In≤63A |
Sectional area of conductor mm² |
1 |
1.5 |
2.5 |
4 |
6 |
10 |
16 |