IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved

Breaking Capacity: Low Voltage Circuit Breakers
Operation: Electric Type
Speed: High-Speed Circuit Breaker
Arc-extinguishing Medium: Air
Installation: Fixed
Type: Circuit Breaker
Samples:
US$ 10/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2016

Suppliers with verified business licenses

Manufacturer/Factory

Basic Info.

Certification
ISO9001-2000, CE, CB, CCC
Model
Lr6-63
Rated Voltage(V)
230/400 VAC
Rated Frequency
50/60Hz
Number of Poles
1p. 1p+N. 2p, 3p, 3p+N, 4p
Transport Package
240 PCS/Carton
Specification
IEC/EN 60898
Trademark
Long Road/OEM
Origin
China
Production Capacity
200, 000 Poles/Month

Product Description

1. MCB Description:
• High breaking capacity and current limiting characteristics;
• Can be installed on standard busbars;
• Dual-function terminals on the upper and lower sides (lift type/open type);
• It can be fixed to the busbar on the upper or lower side;
• With isolation function, it can be used as a main switch;
• Red-green color contact status indicator;
• Wiring terminal guide to prevent wrong wiring;
• 3-position guide rail clip for easy removal from the busbar;
• Complete product specifications;
• Applicable up to 48 V DC
• Rated breaking capacity 6kA in accordance with IEC/EN 60898-1


2. Electrical technical data:
Design according to IEC/EN 60898-1
Characteristic B, C, D
Rated voltage AC 230 / 400V
  DC 48V Single-pole, 2 pole in series: 96VDC
Rated frequency 50/60Hz
Rated current 6,10,16,20,25,32,40,50,63A
Rated current interrupting rating B,C,D curve----6000A
Number of poles 1,1P+N, 2, 3, 3P+N, 4
Endurance ≥ 20,000 operations
Power inlet mode Upcoming
Allowable ambient temperature range -40ºC~75ºC

3.Mechanical technical data:
Per pole width dimension 13mm
Installation method IEC standard rail 35mm
Enclosure protection grade IP20
Dual function terminals on both sides Open type / lift type
Terminal protection Finger and hand safe
Terminal wiring capacity 1-25 mm²
Terminal screw tightening torque 2-2.5 Nm
Busbar thickness 0.8-2 mm
Installation angle function is independent of position

IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved
IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved

IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved


IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved
IEC/En 60898 Residual Current Circuit Breaker Australia SAA Approved

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now